# What should I record before asking for help with an EM132?

> Before contacting SATEC Australia about an EM132, record the label and ordering code, the device info display, the as-found basic settings, the clock comparison, any diagnostic codes and what happened on site. SATEC Australia's advice is to read these without changing anything.

Source page: https://satec-global.com.au/support/articles/em132-support-evidence/

---

EM132 · SUPPORT

# What should I record before asking for help with an EM132?

*[EM132 product illustration]*EM132 product illustration

## Quick Answer

**SATEC Australia's advice** is to record what the meter is and what it is showing before anyone changes it. Collect the label and ordering code, the front-panel device info display, the as-found basic settings, the clock comparison, any diagnostic codes and a short account of what happened. Then contact SATEC Australia technical support through our [contact form](https://satec-global.com.au/contact/).

**SATEC Australia's advice** is also to read only while you gather this. Do not clear diagnostics or communication counters, use the Reset function, set the meter's clock or change its settings. The manuals describe each of these as clearing or changing something in the meter.

## 1. Which Meter It Is

**SATEC Australia's advice:** record the following:

- a clear photograph of the meter's label, and the full ordering code from the purchase records if you have it. See [Which EM132 model and input variant do I have?](https://satec-global.com.au/support/articles/em132-identify-model-variant/) for how to read it;
- whether an expansion module is fitted, and its type if known;
- from the front-panel device info display: the serial number, the device software (firmware) version, the boot version and the communication port settings, exactly as shown.

The manual describes the device info display as service information "that may be required for meter identification and inspection". The EM132 datasheets list two models, the EM132 and the EM132-TP, which has two integral RS-485 ports; the manual does not name the EM132-TP.

## 2. Diagnostic Messages, Recorded Early

The device info display also shows diagnostic messages from the meter's self-test. In PAS, with the meter on-line, open Monitor, select Device Control and then the Device Diagnostics tab. The manual's diagnostic code list is in Appendix H, printed page 188.

The manual says some diagnostic events clear automatically once their cause disappears. **SATEC Australia's advice** is therefore to write down every code as soon as you see it, and photograph the display if you can.

The Device Diagnostics tab has a Clear button that clears the diagnostic events. **SATEC Australia's advice:** do not press it while gathering evidence.

## 3. The As-Found Settings

The basic settings are in PAS under Meter Setup, General Setup, and on the front panel. They include:

- wiring mode;
- PT ratio and PT ratio multiplier;
- CT primary current;
- nominal frequency.

The PAS site for an EM13x meter also holds the CT secondary (5 A or 1 A) chosen for it.

**SATEC Australia's advice:** record these values as they are, and keep them separate from the ordering code. They show how the meter is set up, not which hardware variant it is.

In PAS, Upload Setups updates the site database with the setups currently in the meter, while Send downloads the selected setup to the meter. **SATEC Australia's advice:** do not press Send, or store a changed value on the front panel, while recording. Keeping a copy of the meter's setup is covered in the PAS lesson [Upload the setups, then duplicate the backup](https://satec-global.com.au/support/pas-university/courses/site-config-workflow/lessons/backup-and-duplicate/). That lesson is worked on an EM133-XM; the PAS file steps are shared, but the EM132's setup menus differ.

## 4. The Clock

In PAS, open Monitor and select RTC. The dialog shows the PC time and the meter time together. **SATEC Australia's advice:** record both, and do not set the clock while gathering evidence, so that records made before and after any change can still be lined up. If the clock has been lost or a low-battery code shows, see [Does the EM132 have a replaceable clock backup battery?](https://satec-global.com.au/support/articles/em132-clock-backup-battery/).

## 5. Communications, If That Is The Problem

In PAS, open Monitor, select Device Control and then the Communications tab. The manual describes this tab as showing the GPRS status and the TCP client connection statistics, and its Clear button clears the communication counters. What it shows depends on the communication module and settings in use.

**SATEC Australia's advice:** record what the tab shows and do not press Clear. Also note the port, protocol, device address and baud rate that the master or SCADA system is set to use, so support can compare them with the meter's COM settings on the device info display.

## 6. Logged Data, If Relevant

The manual describes copying the meter's logs to a PC database in PAS under Logs, Upload Logs, with optional From and To dates. Clearing logged files is done from the PAS Reset dialog (Monitor, Reset). The front-panel RESET menu clears maximum demands, the Min/Max log, counters and device diagnostics.

**SATEC Australia's advice:** upload only the logs relevant to the question, note the date range you chose, and do not use the Reset function.

## 7. What Happened

**SATEC Australia's advice:** also describe:

- when the problem started, and whether it is continuous or intermittent;
- any power outage, work on the switchboard, firmware update or settings change around that time;
- what the meter shows compared with what you expected, with readings or screenshots.

**SATEC Australia's advice** is to take photographs of the meter's connections only where the site's own safety procedures allow it. Do not open the meter, and never open an energised CT secondary circuit.

## Manuals And Source Pages

- **EM13X Series Installation and Operation Manual**, BG0491. The cover shows Rev. A15, PDF page 2 is dated August 2024, and the footer on PDF page 4 says Rev. A16. Device info display printed page 77 / PDF page 80; basic setup printed pages 95–96 / PDF pages 98–99; reset printed page 130 / PDF page 133; clock and diagnostics printed page 132 / PDF page 135; communication status printed page 133 / PDF page 136; log upload printed page 146 / PDF page 149; diagnostic codes printed page 188 / PDF page 191. [Open the manual at the device info display in a new tab](https://satec-global.com.au/documentation/EM132-133-installation-operation-manual.pdf#page=80).
- **PAS Getting Started**, BG0337 Rev. A2: sending and uploading setups, page 10. [Open the guide in a new tab](https://satec-global.com.au/documentation/PAS-Getting-Started.pdf#page=10).
- **EM132 product page**: [EM132 multi-function meter](https://satec-global.com.au/solutions/em132-multi-function-meter/).

## Related Help

- [Which EM132 model and input variant do I have?](https://satec-global.com.au/support/articles/em132-identify-model-variant/)
- [Does the EM132 have a replaceable clock backup battery?](https://satec-global.com.au/support/articles/em132-clock-backup-battery/)
- [PAS: creating and identifying a site (worked on an EM235)](https://satec-global.com.au/support/pas-university/courses/site-config-workflow/lessons/create-and-identify/)
- [Knowledge Base home](https://satec-global.com.au/support/#top)

Source review: 22 November 2026.

[Contact SATEC technical support](https://satec-global.com.au/contact/)

[Back to Knowledge Base home](https://satec-global.com.au/support/#top)