# Preparing the EDL175 for a field session

> What the EDL175 manual lists in the kit, how it says to connect the current sensors and set the CT value, and how it says to connect the logger on site.

Source page: https://satec-global.com.au/support/articles/edl175-field-preparation/

---

EDL175 · FIELD SESSION

# Preparing the EDL175 for a field session

*[EDL175 installation and operation manual cover]*EDL175 installation and operation manual cover.

This page collects what the EDL175 manual says about the kit, the current sensors, the CT setting and connecting the logger on site. Battery charging and storage are covered in [Looking after the EDL175 battery](https://satec-global.com.au/support/articles/edl175-battery/).

## The kit

The manual says "The EDL175 parameters include all the measurement and logging capabilities of the PM175 Powermeter". It refers to the PM175 Installation and Operation Manual for the PM175, and to the PAS User's Manual for the PAS software.

The manual's contents list includes:

- EDL175 Installation and Operation Manual
- Series PM175 Installation and Operation Manual
- Series PM175 CD
- Current Clamps Set
- Voltage Probe Set
- Case for Clamps and Cable
- Communications Cable
- Power Supply Cord
- FLEX current sensors
- Connection Cables for FLEX current sensors
- Special cables for current clamps for low current measurement (100mA-10A)

The manual says the standard clamps' primary nominal current is "according to the order specification". **SATEC Australia's advice:** check your kit against your order paperwork, not against this list.

The manual's recommended charge time for the battery is 8 hours. **SATEC Australia's advice:** charge the battery before you leave for site.

## Current sensors

The manual lists four ways to connect the current inputs:

- Regular connection via the terminal block (the same as the terminal block of the PM175).
- Current clamps with a current source output signal, for high current measurement.
- Current clamps with a current source output signal and the special cable, for low current measurement.
- Current clamps with a voltage source output signal, or flexible current sensors with the connection cables for FLEX current sensors.

The manual also says:

- The standard current clamps have a 1A secondary nominal current, and a primary nominal current according to the order specification (120A / 200A / 1000A / 3000A). The maximum EDL175 measured current is 200% of the nominal current.
- The EDL175 can work with all standard FLEX and clamp current sensors that have a voltage output up to 3V RMS.
- "Even if measuring only one phase current, all current sensors must be connected."

Whether the FLEX sensors need their own battery is covered in [Looking after the EDL175 battery](https://satec-global.com.au/support/articles/edl175-battery/).

## The CT setting

The EDL175 manual says to set the wiring mode and CT as for the PM175, referring to "Table 4-1" of the PM175 Installation and Operation Manual or the PAS User's Manual, and to set the PT as in "Section 4.1" of the PM175 manual. The PM175 manual BG0415 Rev. A7 has no Table 4-1. It covers these settings under "Basic Meter Setup" in Chapter 4 (PAS), and in the basic device settings table for the front panel.

The EDL175 manual gives these CT values:

| Measurement (manual heading) |CT value the manual gives |
| Normal Measurement |CT = 1 |
| Direct Measurement (via clamps): all clamps |CT = I1ncl / I2ncl (the clamp nominal primary and secondary currents) |
| Measurement via External CTs Secondary Current, Clamps and Special Cables |(Ip / Is) × (I1ncl / I2ncl) × 0.005, where Ip and Is are the external CT's primary and secondary nominal currents |

The manual's examples for these: a 1000 A/1 A clamp gives CT = 1000, and a 1000/1 clamp on the secondary of a 3000/5 CT gives CT = 3000.

**FLEX sensors and clamps with a voltage output: the manual is inconsistent.** On page 9 it says sensors with "nominal output voltage of 3V require the CT to be set to the nominal primary current", and sensors with "nominal output voltage of 2V require the CT to be set to 150% of the nominal primary current". Its own examples on the same page don't follow those rules: "I1ncl =300A, V2ncl = 2V; CT=150" (the rule would give 450), and "I1ncl =3000A, V2ncl = 3V; CT=1500" (the rule would give 3000).

**SATEC Australia's advice:** if you are using FLEX sensors or clamps with a voltage output, confirm the CT setting with SATEC Australia support before you start recording.

The PM175 manual describes two setup entries on the PM175's primary menu: OPS, to review setup options, and CHG, to change setups or clear accumulated values. In the basic setup menu (bASc), the item Ct is the CT primary current. **SATEC Australia's advice:** to check the CT value already set, use OPS rather than CHG, and read the value without editing it.

## On site

The manual says:

- "The distance between the EDL175 and the current lines must be at least half a meter (1.6 feet) for current lines carrying up to 600A, and at least one meter (3.3 feet) for currents between 600A and 2000A."
- Connect the EDL175 to the AC power supply using the power supply cord, and turn the slide switch ON.
- Connect the voltage probes to the EDL175 through the voltage connectors marked V1/V2/V3/VN, then connect the probes to the line conductors according to the power system configuration.
- "Connect the current sensors first to the EDL175 and then to the measured circuit."
- Connections for relays, status inputs and communications are the same as for the PM175; see the PM175 manual.

**SATEC Australia's advice:** connections to live circuits must be made by a qualified person following your site's electrical safety procedures. Never open the secondary circuit of an energised current transformer.

## Need help?

**SATEC Australia's advice:** if your kit, sensors or settings don't match this page, contact us with the EDL175's serial number and a photograph of your sensors.

Contact SATEC Australia technical support through our [contact form](https://satec-global.com.au/contact/).

Source review: 22 November 2026.
