# What BFM136 identity and diagnostic details should I collect?

> How to record a BFM136's label, serial number, firmware and port settings, read its diagnostics on the display and in PAS, and retrieve its event and data logs before anyone clears or changes anything.

Source page: https://satec-global.com.au/support/articles/bfm136-identity-and-diagnostics/

---

BFM136 · DIAGNOSTICS

# What BFM136 identity and diagnostic details should I collect?

*[BFM136 manufacturer product photograph]*BFM136 manufacturer product photograph

This article covers what the BFM136 branch feeder monitor shows about itself on its display and in PAS: its diagnostic codes, its logs, and its clock. **SATEC Australia's advice:** when a BFM136 reports a fault, stops communicating or gives unexpected readings, record these details before anyone clears the diagnostics, resets logs, changes settings or updates the firmware.

It applies to the BFM136 as described in SATEC's BFM 136 Installation and Operation Manual, BG0394 Rev. A11 (July 2024). Its log capacities and diagnostic code list differ from those in the BFM-II manual, BG0588 Rev. A12. **SATEC Australia's advice:** do not use BFM-II instructions for a BFM136.

## Read the label

The manual shows the BFM136 labels in Figures 1-1a and 1-1b. They carry the ratings, a COM1 "RS-485" field, COM2 tick boxes for "RS-232", "RS-485", "MODEM", "ETHERNET" and "RF", an "S/N" field, and the words "USE ONLY WITH THE SUPPLIED SATEC HACS (CURRENT TRANSFORMER)".

**SATEC Australia's advice:** photograph the whole label, and note the serial number, the COM2 box that is ticked, and the HACS current sensors fitted.

## Read the service display

The BFM136 is provided with "an LCD display and four push buttons". The manual lists these service display pages:

| Page No |Page content |Description |
| 1 |Diagnostics |Device diagnostics. See Diagnostics Display below. |
| 2 |S/N |Device serial number |
| 3 |S/W, Boot |Software version; Boot loader version |
| 4 |COM1 |COM1 port: address and baud rate |
| 5 |COM2 |COM2 port: node address and net ID, or IP address |
| 6 |Ph1 Ph2 Ph3 |Submeter phase current assignments |

The manual says the diagnostics page "is only displayed if errors were detected".

The manual's feature list marks two features with firmware footnotes. "Time-of-Use, 4 energy/demand registers x 6 tariffs" is footnoted "From Firmware version 18.4.1". The "import/export" part of the "Automatic 120–day daily profile for import/export energy and maximum demand readings (total and tariff registers) separate for each submeter" is footnoted "From Firmware version 18.5.1". **SATEC Australia's advice:** record the software and boot loader versions exactly as shown.

The manual says that "The flashing yellow CPU LED shows that the device is operational and is functioning normally", and that the green TX and RX LEDs "flash when the port is receiving or transmitting data" on COM1.

## Addresses

Each active sub-meter is assigned a unique communication address, in sequential order starting with the device base address. The manual says: "Your device is factory preset to address 1 and occupies the range of addresses 1 through 12, configured for 12 three-phase submeters." **SATEC Australia's advice:** record the base address and the sub-meters in use.

For several meters on one network, see [How do I address multiple BFM meters on RS-485 or Ethernet?](https://satec-global.com.au/support/articles/bfm-rs485-ethernet-addressing/)

## Diagnostics

The manual says the device diagnostics status "is stored in a non-volatile register, which may be inspected and cleared via PAS, from the meter display or from a user application". It also says "All diagnostic events with time stamps are also recorded in the device Event log".

In PAS, the diagnostics are viewed or cleared under **Monitor → Device Control**. The manual says: "You must be connected to the BFM136 using the device base address to be able to clear the diagnostics status." **SATEC Australia's advice:** record the codes and retrieve the Event log before anything is cleared.

At power-up, "a start-up diagnostic message is displayed for one second. 'Power Up' indicates a normal power-up sequence."

Appendix F lists these codes:

| Diagnostic Code |Startup Display Message |Description |Reason |
| 2 |RAM/Data Error |Memory/Data error |Hardware failure |
| 3 |WDT Reset |Hardware watchdog reset |Hardware failure |
| 4 |Sampling Fault |Sampling fault |Hardware failure |
| 5 |CPU Exception |CPU exception |Hardware failure |
| 6 |Run-Time Error |Run-time software error |Hardware failure |
| 7 |Software Exception |Software watchdog timeout |Hardware failure |
| 8 |Power Up |Power Down/Up |Loss of power. Normal power-up sequence |
| 9 |External Reset |Warm restart/Device reset |External restart via communications or by firmware upgrade |
| 10 | |Configuration reset |Corrupted setup data has been replaced with the default configuration |
| 11 | |RTC fault |The clock time has been lost |
| 14 | |Expanded memory/Data flash fault |Hardware failure |

The manual's guidance:

- "In the event of a device fault, check the fault reason and clear the device diagnostics."
- "In the event of a time fault, update the device clock."
- "In the event of a configuration reset, check the setup affected by the fault via the device Event log, and then verify the setup data."
- "Hardware failures are normally non-critical recoverable faults that do not cause a system failure but may cause data loss. Hardware failures are often caused by excessive electrical noise in the region of the device."
- "If the device continuously resets itself, contact your local distributor."

## Logs

PAS retrieves the event and data log files from the BFM136 sub-meters and saves them "on your PC in the MS Access database format".

| Log |Manual description |Capacity |
| Event log |"a separate Event log file for each metering submeter"; "All general device events, like device diagnostics, are recorded to the first Event log file that is accessed via the device base address" |"keeps 200 most recent events" (wrap-around) |
| Data log #1 |"one data log file per submeter"; "up to six data parameters per record" |"a maximum of 5000 records per file" (wrap-around) |
| Data log #16 |"the daily profile data file" |The feature list gives an "Automatic 120–day daily profile" |

PAS can clear log files: **Monitor → Reset** clears "maximum demands and log files individually in each submeter". **SATEC Australia's advice:** retrieve the Event log early, and do not clear any log while collecting evidence.

## Clock

The PAS RTC dialog "displays the current PC time and the time in your device. To synchronize the device clock with the PC clock, click Set." **SATEC Australia's advice:** note the difference between the two times before anyone presses Set.

The manual gives the real-time clock accuracy as a typical error of 1 minute per month at 25 °C. Its feature list includes "Internal clock, keeping the clock running over one week without external power".

## Firmware updates

Firmware is downloaded with the PAS Flash Downloader. The manual says "Upgrading is only supported through the Modbus RTU and Modbus/TCP protocols", and that "After upgrading firmware is completed, the device restarts." **SATEC Australia's advice:** retrieve all logs and save the device setup before a firmware update.

## What to send to support

**SATEC Australia's advice:** send SATEC Australia:

- the label photograph and serial number;
- the software and boot loader versions;
- the COM1 and COM2 settings and the base address;
- the diagnostic codes;
- the clock difference;
- the PAS database with the retrieved Event and Data logs;
- a description of what happened and when.

Contact SATEC Australia technical support through our [contact form](https://satec-global.com.au/contact/).

Source review: 22 November 2026.
