# Which BFM-II module combination fits my circuits?

> How to count the current inputs your loads need and match them to the documented standard BFM-II module combinations, including the limit that applies when a Voltage Input Module (VIM) is fitted.

Source page: https://satec-global.com.au/support/articles/bfm-ii-module-combination-capacity/

---

BFM-II · CAPACITY

# Which BFM-II module combination fits my circuits?

*[BFM-II manufacturer product photograph]*BFM-II manufacturer product photograph

The standard BFM-II is modular. The main control module (MCM) has 18 current measurement channels, and the documented combinations add current input modules (CIMs) for up to 54. This page covers counting the inputs your loads need, the documented combinations, and the limit that applies when a Voltage Input Module (VIM) is fitted.

It covers the standard BFM-II energy meter described in the BFM II EM and DFR Operation and Installation Manual, BG0588 Rev. A12. It does not cover the BFM-II DFR, which the manual lists with 12 current measurement channels, or the BFM136.

## Count the current inputs you need

The manual says: "The number of the selected current inputs for a submeter specifies if it will be a single-, two-, or three-phase meter." A single-phase submeter uses 1 input, a two-phase submeter 2 and a three-phase submeter 3.

The manual allows "Any combination of single-, two-, and three-phase consumers … up to a total of 54 current inputs", and up to 54 single-phase, 27 two-phase or 18 three-phase submeters in a single device.

**SATEC Australia's advice:** list every load with its number of phases, and add up the inputs needed.

## Documented combinations without a VIM

| Model |Modules |Current measurement channels |
| BFM-218 |MCM only |18 |
| BFM-224 |MCM + 1 × CIM6 |24 |
| BFM-230 |MCM + 2 × CIM6 |30 |
| BFM-236 |MCM + 1 × CIM18 |36 |
| BFM-242 |MCM + 1 × CIM18 + 1 × CIM6 |42 |
| BFM-254 |MCM + 2 × CIM18 |54 |

These six combinations come from the manual. The datasheets allow at most two CIMs per device.

## If you need a VIM

The Voltage Input Module adds a second set of three-phase voltage inputs, so the BFM-II can meter circuits fed from a parallel power source. Only one VIM can be fitted per device.

With a VIM fitted, no more than one CIM can be used. The factory datasheet says the VIM limits the instrument to 36 current channels, and the factory product page says the maximum is then 12 three-phase channels. Of the combinations above, only BFM-218, BFM-224 and BFM-236 have a single CIM or none.

The installation manual's capacity list does not mention the VIM. The VIM limit comes from the datasheets and the product page.

## A worked example

A switchboard has 10 three-phase loads and 8 single-phase loads, and no VIM is needed.

- Inputs needed: 10 × 3 + 8 × 1 = 38.
- BFM-236 has 36 inputs, which is not enough. BFM-242 (42) and BFM-254 (54) both have enough.
- With a VIM, the most available is 36 inputs, so the same loads would not fit in one BFM-II.

This is arithmetic from the documented capacities, not a recommendation for a particular site.

## Ordering and options

Each CIM is ordered for one sensor type, HACS, RS5 or FLEX, in a 6-input or 18-input version:

| Code |Module |
| C6H-BFM II / C18H-BFM II |6 or 18 inputs, HACS version |
| C6R-BFM II / C18R-BFM II |6 or 18 inputs, RS5 version |
| C6F-BFM II / C18F-BFM II |6 or 18 inputs, FLEX version |
| VIM50Hz / VIM60Hz |Voltage Input Module, 50 Hz or 60 Hz |

What a particular BFM-II supports depends on its ordering code, the modules fitted, its firmware and its configuration. The manual's firmware list says VIM support was added in the V37.3.XX firmware family. **SATEC Australia's advice:** before you add modules to an existing BFM-II, send us its serial number, the modules fitted, the sensor type and the firmware version, and we will check the combination with you.

## Fitted capacity is not the same as configured submeters

The manual says a submeter "remains inactive while there are no current inputs associated with the submeter", or until it is set up as a totalisation submeter. Fitting more inputs does not by itself make submeters active. See [how BFM-II inputs, phases and submeters relate](https://satec-global.com.au/support/articles/bfm-ii-inputs-phases-submeters/) and [how to address multiple BFM meters](https://satec-global.com.au/support/articles/bfm-rs485-ethernet-addressing/).

## Need help?

**SATEC Australia's advice:** contact us through our [contact form](https://satec-global.com.au/contact/).

Source review: 22 November 2026.
