PM180 · APPLICATION NOTE

# PM180 EN 50160:2010 power quality recorder application note

High Performance Analyzer PM180 EN 50160:2010 Power Quality Recorder Application Note

Transcribed from the SATEC document [PM180 Series eXpertmeter EN 50160:2010 Application Note, BB0180 REV.A1, date not printed](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf) (PDF, 37 pages, 1151 KB). Drawings and diagrams are in the PDF. If this page and the PDF differ, the PDF is right; tell us through the [contact form](https://satec-global.com.au/contact/).

## 1 General

The PM180 provides two user-selectable power quality recording options. This application note outlines specific features provided by the EN 50160:2010 PQ recorder.

The accompanying PAS configuration and data acquisition software provides a user with a means for remote configuring the PQ recorder, monitoring, retrieving and reporting EN 50160:2010 compliance statistics data.

See the PM180 Operation Manual for basic information on configuring and operating EN 50160 PQ recorders and available data logging options.

See Section 2 Configuring the EN 50160:2010 PQ Recorder on how to select and configure the PM180 PQ recorder to get measurements and statistics reports.

## 1.1 Features

The EN 50160:2010 PQ recorder provides a user with accurate power quality measurements and statistical reports. The recorder also provides detailed time-stamped event, data and waveform information to allow easy diagnosing and resolving power quality incidents.

The EN 50160:2010 PQ recorder features:

- Monitoring, detecting and recording power quality incidents for all voltage characteristics listed by EN 50160:2010
- Collecting statistical information upon EN 50160:2010 indices including percentiles, maximum values over a period of time and indicative statistics for voltage events
- Printable EN 50160:2010 compliance reports with selectable voltage characteristics, accompanied by optional user information and company logo
- Configurable power quality indices including compliance limits, hysteresis and weekly/daily percentiles in accordance with the requirements of the particular installation

Reference documents:

- EN 50160:2010 Voltage characteristics of electricity supplied by public electricity networks, July 2010, CENELEC.
- CLC/TR 50422:2003 Guide for the application of the European Standard EN 50160, June 2005.
- IEC 61000-4-30 Electromagnetic compatibility (EMC) – Part 4-30: Testing and measurement techniques – Power quality measurements, Edition 3.0, 2015-02.
- IEC 61000-4-7 Electromagnetic compatibility (EMC) – Part 4-7: Testing and measurement techniques – General guide on harmonics and interharmonics measurements and instrumentation, 2nd edition, 2002-08.
- IEC 61000-4-15 Electromagnetic compatibility (EMC) – Part 4-30: Testing and measurement techniques – Flickermeter – Functional and design specifications, Edition 2.0, 2010-08.
- IEC/TR 61000-2-8 Electromagnetic compatibility (EMC) – Part 2-8: Environment – Voltage dips and short interruptions on public electric power supply systems with statistical measurement results, 2002-11.
- IEC TS 62749 Assessment of power quality – Characteristics of electricity supplied by public networks, Edition 1.0, 2015-04
- IEC 62586-1 Power quality measurements in power supply systems – Part 1: Power quality instruments (PQI), Edition 2.0, 2017-03
- IEC 62586-2 Power quality measurements in power supply systems – Part 2: Functional tests and uncertainty requirements, Edition 2.0, 2017-03

## 1.2 Measurement Techniques

## 1.2.1 Power Quality Monitoring and Recording

The PM180 PQ recorder measures, evaluates and collects power quality information as defined and described in EN 50160:2010. A detailed description of the evaluation techniques used by the PM180 is given in Annex A.

Whenever IEC 61000-4-30 techniques conflict with EN 50160:2010 normative requirements, a user is given an option to choose a preferable method.

## Monitoring Thresholds and Compliance Limits

Since PQ monitoring is intended both for network power quality assessment and for troubleshooting of power quality related problems, the PQ recorder provides collecting of power quality compliance statistics and individual recording of all power quality related events based on predefined detection thresholds and limits.

The monitoring thresholds and compliance limits are normally based on power quality indices provided by EN 50160:2010, but can be changed by the user via the EN 50160:2010 PQ Recorder setup to meet his particular installation’s requirements.

For voltage parameters that are characterized by statistical power quality indices like percentiles over a period of time, or for which only indicative statistics is collected, like dips, swells and interruptions, the detection thresholds are defined by high and low normally permissible limits parameters.

For voltage characteristics which compliance with the standard is also characterized by maximum and minimum values over a period of time, like frequency and supply voltage variations, the compliance limits are extended by the high and low maximum permissible limits parameters.

## PQ Event Recording

Whenever a monitored parameter exceeds its monitoring/detection threshold, a power quality related event is recorded to the PQ event log file provided with indication of the affected parameter, channel, start and end timestamps and a maximum/minimum magnitude recorded during the event.

For voltage characteristics provided with dual compliance limits, a user can choose which one is to be used as a detection threshold for monitoring PQ related events.

Any monitored parameter can be individually enabled or disabled for event recoding via the EN 50160:2010 PQ Recorder setup, as well as event recording can be globally disabled or enabled in the device. Disabling of PQ event recording, partially or entirely, does not affect evaluation of statistical power quality data collected for EN 50160:2010 compliance reports.

## Disturbance Waveforms Recording

Power quality events can be accompanied by voltage and current waveforms recorded at the beginning, during and after the event. The number of pre-event and post-event cycles and the desired sample rate can be configured via the Waveform Recorder setup.

Waveform log files #7 and #8 are used by default for recording power quality related waveforms, but those can be changed to any other log file via the EN 50160:2010 PQ Recorder setup. In presence of the fast transient module, transient waveforms are re-directed to Waveform Log #6 that is automatically re-configured in this case for a higher sample rate.

Waveform recording is enabled by default for voltage dips, swells, interruptions and transients and can be individually enabled for other power quality parameters via the EN 50160:2010 PQ Recorder setup.

## Data Trend Recording

For troubleshooting and testing reasons, the PQ recorder provides an additional feature that allows synchronous recording a set of selected measured data, like RMS volts and currents, signaling voltages, harmonics characteristics, and others, before, during and after a power quality event while using different time envelopes dependent on the event duration.

The recorder can start at half-cycle measurements and, as an event continues more time, to automatically move to longer time envelopes of up to 10-min aggregated measurements, and then return to a faster sample rate at the end of the event. The recording duration for each time envelope and the number of cycles to be recorded before and after the event can be configured via the EN 50160:2010 PQ Recorder setup.

Data log file #14 is dedicated for PQ event data trends. By default, no data trending is enabled in the PM180, but can be individually enabled and configured for any parameter using desired time aggregation intervals.

See Annex E for the list of parameters available for data trends synchronized with the PQ recorder.

## Compliance Statistics Recording

EN 50160:2010 compliance statistics are automatically collected during weekly/daily evaluation periods unless evaluation is intentionally disabled via the EN 50160:2010 Advanced Setup. At the end of every evaluation period, collected statistical data is recorded to the dedicated log files. For testing reasons, intermediate statistics can be retrieved online and inspected at any time during the current evaluation period without affecting final compliance reports.

Data log files #10 and #11 are automatically configured in the PM180 for a 260-week statistics recording based on weekly evaluation periods, or for 260 days assuming daily statistics evaluation. The file size can be changed via the Log Memory setup dialog in case that data should be stored in the device for a longer time.

A weekly or daily evaluation period for collecting and recording statistical data can be selected, and the week day and time on which a calendar week starts can be configured via the EN 50160:2010 Advanced Setup.

## 1.2.2 Special Features

## Flagging

During a voltage event like a dip, swell or interruption, the measurements for other voltage characteristics might produce unreliable values. The flagging concept avoids counting a single event more than once in different voltage parameters.

If, during a given time interval, a voltage event is detected, all voltage characteristics aggregated during this interval are flagged and are not included into statistical data. If, during a given time interval, any value is flagged, the aggregated value which includes that value is also be flagged.

Flagged data is not included into the EN 50160:2010 compliance statistics and PQ incidents are normally not recorded to the PQ event log file. For testing or troubleshooting reasons, recording flagged data can be enabled via the EN 50160:2010 Advanced Setup.

When enabled, flagged events appear in the PQ event log reports being marked by an asterisk.

## Polyphase Aggregation

In a three-phase system, polyphase aggregation is applied to voltage dips and swells. A voltage dip or a swell is counted as one equivalent polyphase event regardless of the shape and number of phases affected and is characterized by a single duration.

The dip/swell magnitude on each affected phase during a polyphase event is individually recorded to the PQ event log file.

## Time Aggregation

Reclosing operations can result in multiple voltage dips or interruptions from the same primary event. It can be misleading to count these disturbances as separate events.

To take account of this effect, the concept of time aggregation is applied for statistical analysis of voltage dips, swells and interruptions. Multiple successive events occurring within a limited interval of time may be counted as an equivalent event with equivalent magnitude and duration. For example, all voltage dips within a defined time interval can be counted as one single event whose magnitude and duration are those of the most severe dip observed during this interval.

Time aggregation is normally disabled in the PM180 and can be enabled by specifying a non-zero time aggregation interval from 1 to 180 s via the EN 50160:2010 Advanced Setup.

Regardless of applying time aggregation, each individual voltage event with its magnitude and duration is recorded to the device PQ event log file to allow further troubleshooting power quality related problems.

## 1.2.3 IEC 61000-4-30 Related Features

For use in specific troubleshooting or statistical applications based on IEC 61000-3-40 methods but requiring a different set of power quality parameters or power quality indices than those listed in EN 50160, the PM180 provides additional measurements like magnitude of coincident currents, harmonic and interharmonic currents, and data aggregation over time intervals listed in IEC 61000-4-30.

## Data Aggregation

Though the EN 50160:2010 power quality indices require measurement aggregation over well-defined time intervals for each voltage characteristic, the PM180 also provides measurement aggregation over time intervals listed in IEC 61000-4-30, mostly for testing reasons.

10/12–cycle, 150/180-cycle, 10-min and 2-hour aggregated power quality related data, like voltages, currents, frequency, unbalance and total harmonics and interharmonics, are available for monitoring and recording.

The integration interval for harmonic and interharmonic voltages and currents intended for monitoring can be selected via the EN 50160:2010 Advanced Setup. By default, harmonic and interharmonic voltage and current readings represent data measured over non-overlapping 10/12-cycle intervals.

## Coincident Currents

Current and current harmonic and interharmonic measurements are not listed by EN 5010:2010 indices and not evaluated for EN 50160:2010 compliance statistics, but provided as a supplement to voltage measurements.

Coincident currents can be recorded in the PQ event log along with the corresponding voltage channels for voltage dips, swells, interruptions and voltage variations with same timing determined by corresponding voltage event. Recording coincident currents is normally disabled and can be enabled via the EN 50160:2010 Advanced Setup.

## Time Stamping

For testing reasons, where power quality related data is to be accompanied by a timestamp, the PM180 provides a synchronous polyphase timestamp for latest available 10/12-cycle measurements that can also be applied to all other composite intervals based on these measurements, as well as per channel timestamps for Urms(1/2) related voltage measurements commencing at a fundamental zero crossing. They are available for monitoring and recording via the present online PQ data group of parameters (see Annex D).

## Block Numbering

Block numbering of 10/12-cycle and 150/180-cycle measurements within each 10-min interval is provided for IEC 61000-4-30 testing reasons (see Annex D).

The block numbers are updated when new data evaluated over the corresponding aggregation interval is available. Block numbers can be effectively used for synchronous and non-overlapping recording of the related power quality data by taking them as setpoint triggers along with a delta operator that responds to a trigger parameter change.

## Flagging Information

Flagging information is given for all aggregation intervals and is indicated by the corresponding parameters in the present PQ data group (see Annex D). It can be used for testing reasons or accompany power quality related data while monitoring and recording.

Each flag holds its status until the corresponding aggregation interval is validated.

## 2 Configuring the EN 50160:2010 PQ Recorder

See the PM180 Operation Manual for common instructions on configuring your device. The following sections outline specific implementation details for operating the EN 50160:2010 PQ recorder.

## 2.1 EN 50160:2010 Recording Option

To get measurements and statistics reports, select the EN 50160:2010 PQ option via the General Setup/Device Options setup dialog.

## 2.2 Clearing EN 50160:2010 Evaluation Counters

The present contents of the EN 50160 evaluation counters may include undesirable statistical data collected during device testing and deployment that can appear in compliance statistics reports. It is recommended to clear PQ counters before starting your EN 50160 evaluation.

To clear the EN 50160 evaluation counters, select Reset from the Monitor menu, click Clear Operation/Event Counters, check the PQ Counters box, and then click OK and confirm your command.

## 2.3 General Power Quality Related Settings

The following device settings affect EN 50160 evaluation and should be checked prior to running the PQ recorder.

## Reference Voltage

As the general approach of EN 50160, all voltage characteristics are referenced to the nominal network voltage that shall be specified by the secondary line-to-line voltage parameter via the Basic setup before running the PQ recorder.

## Reference Frequency

The nominal line frequency is used as a reference for evaluation of power frequency and for selecting the appropriate measurement time interval for all power quality related measurements. It also affects characteristics of digital filters used by some evaluation methods like flicker measurements.

## 2.4 Configuring the EN 50160:2010 PQ Event Recorder

To configure the EN 50160:2010 PQ recorder, select Memory/Log in the Meter Setup Menu and then click on the EN 50160:2010 PQ Recorder tab.

This setup allows you to adjust the detection thresholds and compliance limits for specific voltage characteristics and to select and configure options for related event, waveform and data trend recording.

The picture below shows the PQ recorder setup dialog with the default factory settings. Use the horizontal scroll bar to move between the two parts of the dialog window.

See Table 2-1 for the available configuration options. See Section 1.2.1 Power Quality Monitoring and Recording for information on how your settings may affect operation of the PQ recorder.

NOTE: When testing the device for compliance with the corresponding standards, some tests may cause generating a large amount of power quality related events that can put an excessive load on the device recorders and thus affect operation of other features in your device. To avoid undesirable effects, you can uncheck the Recorder Enabled box to temporary disable operation of the EN 50160:2010 PQ recorder.

PM180 - Log Setup dialog, EN 50160:2010 PQ Recorder tab with default factory settings, first part (PQ Events and Recording: Thresholds, PQ Log, Waveform Log). Drawing not reproduced on this page. [See page 9 of the PDF](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf#page=9).

PM180 - Log Setup dialog, EN 50160:2010 PQ Recorder tab with default factory settings, second part (PQ Events and Recording: Waveform Log, Data/RMS Trend - Time Envelopes and Maximum Durations). Drawing not reproduced on this page. [See page 9 of the PDF](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf#page=9).

Table 2-1 EN 50160:2010 PQ recorder setup options
| Option |Range |Description |
| Thresholds | | |
| Percentile rank, % |0-100.0% |Defines the percentile rank for evaluation percentiles over a period of time |
| High norm. perm. |-20.00-200.00% |High normally permissible limit. Defines the higher detection threshold and a compliance (percentile) limit for parameter evaluation, in percent of the reference value |
| Low norm. perm. |-20.00-200.00% |Low normally permissible limit. Defines the lower detection threshold and a compliance (percentile) limit for parameter evaluation, in percent of the reference value |
| High max. perm. |-20.00-200.00% |High maximum permissible limit. Defines the maximum allowed compliance limit for parameter evaluation, in percent of the reference value |
| Low max. perm. |-20.00-200.00% |Low maximum permissible limit. Defines the minimum allowed compliance limit for parameter evaluation, in percent of the reference value |
| Hysteresis, % |0-50.0% |Defines the hysteresis for a PQ parameter, in percent of the reference value or threshold |
| PQ Log | | |
| On norm. perm. |Checked
Unchecked |Enables recording power quality related events for a specific voltage characteristic on exceeding the normally permissible limit |
| On max. perm. |Checked
Unchecked |Enables recording power quality related events for a specific voltage characteristic on exceeding the maximum permissible limit |
| Waveform Log | | |
| On start |Checked
Unchecked |Enables coincident waveform recording on detection of a power quality event |
| On end |Checked
Unchecked |Enables triggering waveform recording after a power quality event ends |
| Log No. |1-8 |Specifies a waveform log file for waveform recording |
| Data/RMS trend – Time envelopes and Maximum Durations | | |
| Enable |Checked
Unchecked |Enables recording of a coincident data trend during power quality related events |
| 1/2-cyc, cycles |0-1000 cycles |Maximum duration of data recording at a half-cycle rate |
| 0.2-s, seconds |0-1000 s |Maximum duration of data recording at a 0.2-second rate |
| 3-s, minutes |0-1000 minutes |Maximum duration of data recording at a 3-second rate |
| 10-min, hours |0-1000 hours |Maximum duration of data recording at a 10-minute rate |
| Before, Cycles |0-20 cycles |The number of cycles to be recorded prior to the event at a half-cycle rate |
| After, Cycles |0-20 cycles |The number of cycles to be recorded after the event at a half-cycle rate |
| Log No. |14 |Indicates a data log file for coincident data recording |

## 2.5 Configuring EN 50160:2010 Advanced Options

To configure the EN 50160:2010 recording options or enable additional recording features, select Memory/Log in the Meter Setup Menu and then click on the EN 50160:2010 Advanced Options tab.

The picture below shows a setup dialog screen with the default factory settings. See Table 2-2 for the available options and their limits.

See Section 1.2 Measurement Techniques for information on the advanced recording options and operation of the PQ recorder.

PM180 - Log Setup dialog, EN 50160:2010 Advanced Setup tab with default factory settings. Drawing not reproduced on this page. [See page 11 of the PDF](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf#page=11).

Table 2-2 EN 50160:2010 advanced setup options
| Option |Range |Default |Description |
| Compliance Statistics | | | |
| Evaluation |Disabled, Enabled |Enabled |Enables the EN 50160:2010 statistics evaluation |
| Evaluation Period |Daily, Weekly |Weekly |Defines the EN 50160:2010 statistics evaluation period |
| First Day of the Week |Sunday-Saturday |Sunday |Defines the first day of the week for statistics evaluated on a weekly basis |
| Start Time |00:00-23:00 |00:00 |Defines the start time of the evaluation period |
| Recording Options | | | |
| Record Flagged Data |Disabled, Enabled |Disabled |Enables recording flagged events to the PQ event log. Fagged data is marked by an asterisk in the PQ log reports. |
| Record Coincident Currents |Disabled, Enabled |Disabled |Enables recording coincident currents. If enabled, the corresponding currents with same timing will be recorded to the PQ event log along with the corresponding voltage channels in case of a voltage dip, swell or voltage variation event. |
| Rapid Voltage Changes | | | |
| Minimum Steady State Time |3 s, 1 s, 100/120 1/2-cyc. |100/120 1/2-cyc. |Defines the minimum time interval for voltages to stay within the detection threshold to be considered a steady-state condition, and the corresponding voltage change detection method |
| Max. Repetition Rate |0=any, 1-10 |0 (any) |Defines the maximum repetition rate in variations per evaluation interval (equal or less than) for rapid voltage changes. Voltage changes at higher rates will not be classified since they would be subject for flicker evaluation |
| Evaluation Interval |1-60 min |60 |Defines the time interval for periodic evaluation of rapid voltage changes. If the maximum repetition rate is set to a non-zero value, the evaluation and recording of the rapid voltage changes will be done at the end of each evaluation interval. |
| Flicker | | | |
| Pst Period |1-10 min |10 min |Defines the period of time for the short-term flicker evaluation. The standard setting of 10 minutes can be temporarily changed in the device for testing purposes |
| Harmonic Voltage | | | |
| THD, up to order |25-50 |40 |Defines the highest harmonic order included in the THD evaluation |
| Harmonics, up to order |25-50 |25 |Defines the highest harmonic order for evaluation of the harmonic voltages |
| Interharmonic Voltage | | | |
| Evaluation |Disabled, Enabled |Disabled |Enables the evaluation of interharmonic voltages |
| THD, up to order |25-50 |40 |Defines the highest interharmonic order included in the interharmonic THD evaluation |
| Interharmonics, up to order |25-50 |25 |Defines the highest interharmonic order for evaluation of the interharmonic voltages |
| Mains Signaling Voltage | | | |
| Evaluation |Disabled, Enabled |Disabled |Enables the evaluation of the mains signaling voltages |
| 1st Signaling Frequency |110-3000 Hz |183.0 Hz |Specifies the mains signaling frequency for the compliance evaluation |
| 2nd Signaling Frequency |110-3000 Hz |191.0 Hz |Specifies the mains signaling frequency for the compliance evaluation |
| 3rd Signaling Frequency |110-3000 Hz |217.0 Hz |Specifies the mains signaling frequency for the compliance evaluation |
| 4th Signaling Frequency |110-3000 Hz |317.0 Hz |Specifies the mains signaling frequency for the compliance evaluation |
| Aggregation Interval |3 s (150/180 cyc.), 0.2 s (10/12 cyc.) |3 s (150/180 cyc.) |Defines the aggregation time for interharmonic bins used in mains signaling voltage measurements |
| Voltage Events | | | |
| Time Aggregation Interval |0-180 s |0 |Defines the aggregation time for time-aggregated voltage events: voltage interruptions, dips and swells. Time aggregation does not apply with a zero interval. |
| Data Monitoring Options | | | |
| Harmonics Aggregation Interval |0.2 s (10/12 cyc.)
3 s (150/180 cyc.)
10 min
2 h |0.2 s (10/12 cyc.) |Defines the aggregation interval for monitoring voltage and current harmonics and interharmonics. The default 10/12-cycle interval can be changed to higher values for testing purposes. The setting only applies to direct harmonic and interharmonic readings and does not affect EN 50160 evaluation statistics. |

## 2.6 Configuring EN 50160:2010 Harmonics Limits

To configure the EN 50160:2010 harmonics and interharmonics compliance limits, select Memory/Log in the Meter Setup Menu and then click on the EN 50160:2010 Harmonics Setup tab.

This setup allows you to define or change detection thresholds and standard compliance limits for individual voltage harmonics and interharmonics.

Since compliance indices for interharmonics are not defined in EN 50160:2010, the interharmonic compliance limits are not provided and interharmonics evaluation in your device is disabled by default. To allow collecting interharmonics compliance statistics, define the compliance limits for individual interharmonics using your local power quality indices and enable interharmonics evaluation via the EN 50160:2010 Advanced Setup.

The picture below shows factory pre-configured settings.

PM180 - Log Setup dialog, EN 50160:2010 Harmonics Setup tab (Harmonic Voltage Limits, % and Interharmonic Voltage Limits, %). Drawing not reproduced on this page. [See page 13 of the PDF](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf#page=13).

The default settings contain values of individual harmonic voltages specified by the standard for low-voltage networks. To automatically pre-set compliance limits for a medium-voltage or high-voltage network, ensure that the nominal voltage and PT ratio settings in your device’s Basic Setup match the actual network characteristics, and then click on the Default button.

## 3 Operating the EN 50160:2010 PQ Recorder

## 3.1.1 Retrieving EN 50160:2010 Event and Statistics Files

See the PM180 Operation Manual for information on retrieving EN 50160:2010 PQ event log, compliance statistics and online statistics files.

## 3.1.2 Getting EN 50160:2010 PQ Event Reports

See the PM180 Operation Manual for detailed information on how to get PQ event reports and on available viewing and printing options.

Annex F provides an example of the EN 50160:2010 PQ event report.

## 3.1.3 Getting EN 50160:2010 Compliance Reports

See the PM180 Operation Manual for information on viewing, editing and printing options for EN 50160:2010 compliance statistics and online statistics reports.

An example of the EN 50160:2010 compliance report is given in Annex G.

## Annex A EN 50160:2010 Evaluation and Recording

## A.1 EN 50160:2010 Background

## Scope of EN 50160:2010

EN 50160:2010 defines main characteristics of the voltage in public low, medium and high voltage electricity networks, which can be expected to remain within limits or values specified by the standard. The different aspects covered by the standard are exclusively related to the following voltage characteristics: frequency, magnitude, waveform and symmetry of the line voltages

The standard is applicable only under normal operating conditions including correct operation of the protection devices in the case of a fault in the network (blowing of a fuse, operation of a circuit-breaker etc.) or changes in network configuration. The standard does not apply under abnormal conditions like maintenance and construction works or other exceptional situations, in particular exceptional weather conditions, power shortages, third party interference or industrial actions.

The voltage characteristics are evaluated using a statistical approach. The standard and its referenced publications specify for each voltage characteristic:

- Method of evaluation
- Time aggregation interval for measurements
- Observation period
- Statistical indication of the probability of not exceeding a specified limit (percentiles)
- Compliance limits or indicative values within which any customer can expect a voltage characteristic to remain

The voltage characteristics covered by the standard are divided into two groups:

- Characteristics for which limit values are specified.
- Characteristics for which only indicative values are given.

Measurement methods to be applied in the standard are described in IEC 61000-4-30, IEC 61000-4-7 and IEC 61000-4-15. Some indicative values for voltage dips and short interruptions are given in IEC/TR 61000-2-8.

## Voltage Characteristics

For the following voltage characteristics, the standard provides definite limits that can be complied with for most of the time considering the possibility of relatively rare excursions beyond limits:

- Power frequency
- Supply voltage variations
- Single rapid voltage changes
- Flicker
- Supply voltage unbalance
- Harmonic voltages
- Interharmonic voltages
- Mains signaling voltages

Table A-1 indicates the time aggregation intervals applied to different voltage parameters and reference compliance limits specified by the standard for the characteristics with definite limits. Limits are set with a view to compliance for a percentage of the observation time.

Table A-1 Reference compliance limits for voltage characteristics
| Voltage characteristic |Aggregation interval |Compliance, % of the time |Observation period |
| Power frequency |10 s |Synchronous connection:
±1% for 99.5% of a year
+4/-6% for 100% of the time
Asynchronous connection:
±2% for 95% of a week
±15% for 100% of the time |Week, year |
| Supply voltage variations |10 min |Low voltage:
±10% Un for 95% of the time
+10%/-15% Un for 100% of the time
Medium voltage:
±10% Un for 99% of the time
±15% Un for 100% of the time
High voltage:
Subject to individual contracts |Week |
| Single rapid voltage changes | |≤4-5% Un (up to 10% Un), only indicative values are given |Day |
| Flicker |10 min |Plt ≤ 1 for 95% of the time |Week |
| Voltage unbalance |10 min |≤2-3% for 95% of the time |Week |
| THD |10 min |Low and medium voltage:
≤ 8 for 95% of the time
High voltage:
Under consideration |Week |
| Harmonic voltages |10 min |EN 50160:2010, Tables 1, 4, 7 depending on the supply network voltage |Week |
| Interharmonic voltages |10 min |Under consideration |Week |
| Mains signaling voltage |3 s |Within “Meister-curve” for 99% of the time, EN 50160:2010, Figures 1, 2 |Day |

Generally, an observation period of one week is chosen because it is the shortest interval to obtain reproducible measurement results. Limits are set with a view to compliance for a percentage of the observation time, e.g. 95% of the observations in any period of one week.

In the case of supply voltage and power frequency variations, further limits are specified within which the average measurements shall remain for 100% of the time.

Compliance limits for supply voltage variations, single rapid voltage changes and signaling voltages are given in percentage of the network nominal voltage. Compliance limits for power frequency are given in percentage of the nominal network frequency.

NOTES:

- For single rapid voltage changes, only indicative values are given for the time being.
- For some specific parameters, national regulations may define stricter limits.
- Compliance limits given in the standard may be superseded in total or in part by the terms of a contract between the user and the network operator.

## Voltage Events

For the remaining characteristics of the voltage, by their unpredictable nature, the standard gives only indicative values, which are intended to provide users with information on the range of magnitude which can be expected. Those are called voltage events and comprise:

- Short and long voltage interruptions
- Voltage dips
- Voltage swells
- Transient overvoltages

Table A-2 shows typical detection thresholds and durations for the voltage events specified by the standard.

Table A-2 Reference thresholds and durations for voltage events
| Voltage event |Threshold and duration |Observation period |
| Short voltage interruptions |<5% Un on all phases, <= 3 min |Year |
| Long voltage interruptions |<5% Un on all phases, > 3 min |Year |
| Voltage dips |<90% Un on any phase, <= 1 min |Year |
| Voltage swells |>110% Un, <= 1 min |Year |
| Transient overvoltages |>20% Un, peak, <= 10 ms |Year |

The basic measurement for detecting voltage interruptions, dips and swells is Urms(1/2) – a value of the RMS voltage measured over 1 cycle, commencing at a fundamental zero crossing and refreshed each half-cycle. Typical hysteresis for voltage events is 2% Un.

Voltage events are classified by their duration and magnitude in percentage of the nominal network voltage. Collected voltage dips and swells event statistics are classified and represented according to the tables 2, 3, 5, 6, 8, and 9 given in EN 50160:2010.

## A.2 EN 50160:2010 Evaluation Techniques

This section describes methods used for evaluating voltage characteristics.

## Power Frequency

## Method of Evaluation

The basic frequency measurement is the mean value of the frequency over fixed time intervals of 10 seconds under normal operating conditions.

A frequency variation is not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

## Target Values

The compliance limits for frequency variations given in the EN 50160:2010 are as follows:

For synchronous connections:

50Hz ±1% for 99.5% of a year

50Hz +4/-6% for 100% of the time

For asynchronous connections:

50Hz ±2% for 95% of a week

50Hz ±15% for 100% of the time

The same limits are used for 60Hz systems.

## Supply Voltage Variations

This characteristic defines slow variations of steady state supply voltage magnitude.

## Method of Evaluation

The basic supply voltage magnitude measurement is the RMS value of the steady state voltage over a period of 10 minutes under normal operating conditions.

A voltage variation is not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

## Target Values

The compliance limits for voltage variations given in the EN 50160:2010 are as follows:

Low voltage networks:

±10% Un for 95% of a week

+10%/-15% Un for 100% of the time

Medium voltage networks:

±10% Un for 99% of a week

±15% Un for 100% of the time

High voltage networks:

Subject to individual contracts

## Single Rapid Voltage Changes

Rapid voltage changes are sudden but relatively weak voltage variations between two steady state voltage levels. The maximum rate of rapid voltage changes in normally once per hour or less. Voltage variations repeating more than once an hour are usually accounted by flicker. To avoid counting excessive flicker by rapid voltage changes, the maximum rate of voltage changes in variations (1 to 10) per an evaluation interval (from 1 min to an hour) can be limited and configured in the meter via the EN 50160:2010 Advanced Setup.

## Method of Evaluation

The PQ recorder provides two methods for evaluation of rapid voltage changes based either on RMS value of voltage over a period of 1 or 3 seconds, or on the arithmetic mean of 100/120 consecutive Urms(1/2) values. The desired method can be selected via the EN 50160:2010 Advanced Setup by defining the minimum steady-state measurement time for detecting a voltage change.

Option 1: The recorder establishes the maximum difference of the RMS voltage between two intervals selected from three consecutive 3-second or 1-second intervals and compares it with the target compliance limit.

Option 2: The voltage change is detected as guided in IEC 61000-4-30 Clause 5.11.2 by establishing a difference between every Urms(1/2) measurement and the arithmetic mean of the preceding 100/120 Urms(1/2) values and comparing it with the target compliance limit (detection threshold). Along with the steady-state voltage change included into statistics, the recorder provides also an indication of the maximum difference between any of the Urms(1/2) values during the event and the final steady-state voltage level.

The rate of rapid voltage changes is not limited by default. To limit evaluation of voltage changes caused by flicker, define a non-zero maximum allowed repetition rate and a time period for counting a rate of changes.

A rapid voltage change is not classified if the rate of changes exceeds the predefined value (if defined), or crosses a dip or swell threshold, as it would be considered a voltage dip or a voltage swell.

## Target Values

Under normal operating conditions the magnitude of rapid voltage changes (once per hour or less) should generally not exceed 5% of nominal voltage in LV networks, and 4% in MV networks. In some circumstances, like in systems where equipment switching must be carried out to meet supply system or load requirements, it can reach 10%Un in LV networks, and 6%Un in MV networks.

## Flicker

Flicker expresses the visual discomfort caused by repetitive changes of brightness in lightning subjected to fluctuations of the supply voltage. Flicker is indicated by the long-term flicker severity parameter Plt, which is evaluated every 2 hours.

## Method of Evaluation

The basic measurement is the short-term flicker severity indicator Pst, evaluated each 10 minutes. The indicative long-term flicker severity Plt is evaluated from 12 consecutive Pst values commencing at even-numbered 2-hour intervals. For testing purposes, the Pst period can be temporarily changed in the meter in the range of 1 to 10 minutes via the EN 50160:2010 Advanced Setup.

Pst values are not classified during intervals when the supply voltage magnitude exceeds a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

Plt is not evaluated if any of the included Pst intervals is flagged.

## Target Values

The flicker compliance limit given in the EN 50160:2010 is:

Plt ≤ 1 for 95% of a week

The Plt compliance limit can be changed in the meter via the EN50160 PQ Recorder setup.

## Voltage Unbalance

This characteristic defines the magnitude and/or phase asymmetries of three-phase steady state supply voltage.

## Method of Evaluation

The basic measurement is the RMS value of the steady state voltage unbalance over a period of 10 minutes under normal operating conditions. It is defined via symmetrical components as the negative sequence component expressed in percent of the positive sequence component.

Voltage unbalance is not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

## Target Values

The compliance limit for voltage unbalance given in the EN 50160:2010 is:

≤ 2% (≤ 3% in some areas) for 95% of a week

## Harmonic Voltages

## Method of Evaluation

The basic measurements are individual harmonic voltages expressed in percent of the fundamental voltage and the total harmonic distortion factor (THD) aggregated over a period of 10 minutes.

Harmonic voltages are evaluated based on 10/12-cycle gapless subgroup measurements. The THD is calculated as the subgroup total harmonic distortion.

Individual harmonic voltages are normally evaluated up to order 25 and the THD is calculated including all harmonics up to order 40 as required by EN 50160:2010. The order of the highest harmonic for both can be configured from 25 to 50 via the EN 50160:2010 Advanced Setup.

Harmonic voltages are not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

## Target Values

The ranges of harmonic voltages given in the EN50160 are:

Low voltage networks:

THD ≤ 8 for 95% of a week

Individual harmonic voltages shall be less than or equal to the values given in Table 1 EN 50160:2010 for 95% of a week.

Medium voltage networks:

THD ≤ 8 for 95% of a week

Individual harmonic voltages shall be less than or equal to the values given in Table 4 EN 50160:2010 for 95% of a week.

High voltage networks:

THD limit is under consideration

Individual harmonic voltages shall be less than or equal to the indicative values given in Table 7 EN 50160:2010 for 95% of a week.

Compliance limits for the THD and individual harmonics can be changed in the meter via the EN 50160:2010 PQ Recorder setup and via the EN 50160:2010 Harmonics setup.

## Interharmonic Voltages

## Method of Evaluation

This feature is normally disabled in the meter and may be enabled via the EN 50160:2010 Advanced Setup.

The basic measurements are individual interharmonic voltages expressed in percent of the fundamental voltage aggregated over a period of 10 minutes.

Interharmonic voltages are evaluated based on 10/12-cycle gapless interharmonic centered subgroup measurements. The total interharmonic distortion is calculated as the subgroup total interharmonic distortion.

The highest interharmonic order for evaluating individual interharmonic voltages and total interharmonic distortion can be selected in the meter via the EN50160 Advanced setup.

Interharmonic voltages are not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

## Target Values

EN 50160:2010 compliance limits for interharmonic voltages are still under consideration. User assigned levels can be configured via the EN 50160:2010 Harmonics setup.

## Mains Signaling Voltage

This characteristic defines the magnitude of the signal voltages used in some countries for signal transmission over public supply networks. The meter can evaluate ripple control signaling voltages in a frequency range from 100 Hz to 3 kHz.

## Method of Evaluation

This feature is normally disabled in the meter since it is not commonly used. It can be enabled and up to 4 signaling frequencies can be selected for monitoring via the EN 50160:2010 Advanced Setup.

The basic measurements for mains signaling voltage can be selected by the aggregation interval setting via the EN 50160:2010 Advanced Setup:

Option 1: 3-second (150/180-cycle) mean value of signal voltages.

Option 2: 10/12-cycle value of signal voltages.

In both cases, the measurement method is based on the root of the sum of the squares of the 4 nearest 10/12-cycle RMS value interharmonic bins.

The EN 50160:2010 detection thresholds and compliance levels for signaling voltages are given by the so-called “Meister-curve” which defines the maximum permissible ripple control voltages in LV and MV networks.

Set to zero the detection threshold for signaling voltages in the EN 50160:2010 PQ recorder setup (factory default) to force using the Meister-curve compliance levels.

For IEC 61000-4-30 testing reasons, the detection threshold can be set to a constant level by defining a non-zero threshold value in percent of the nominal voltage.

Signaling voltages are not evaluated if the supply voltage crosses a voltage tolerance limit (±20% Un) or the calculation interval is flagged.

## Target Values

The 3-second mean value of the signal voltages shall be less or equal to the specified limits for 99% of a day.

For HV networks, no values are given for mains signaling voltages.

## Voltage Interruptions

Voltage interruptions correspond to temporary loss of supply voltage on all phases lasting less than or equal to 3 minutes in the event of short interruptions, and more than 3 minutes for long interruptions.

## Method of Evaluation

The voltage interruption is detected when the voltages on all phases fall below the interruption threshold (IEC 61000-4-30) that is specified by the EN 50160:2010 at a level of 5%Un. The interruption threshold can be changed in the meter via the EN 50160:2010 PQ Recorder setup.

Time aggregation of multiple successive interruptions can be applied.

The basic voltage measurement for voltage interruptions is Urms(1/2).

## Statistical Survey

Statistical data is classified by interruption duration. EN 50160:2010 does not provide a classification method for voltage interruptions. Some indicative data can be found in IEC/TR 61000-2-8. The PM180 EN 50160:2010 PQ recorder classifies interruptions according to Table A-3.

Table A-3 Classification of voltage interruptions according to durations
| Residual voltage u, %Un |Duration t, s | | | | | | |
| |t <= 0.5 |0.5 < t <= 1 |1 < t <= 5 |5 < t <= 20 |20 < t <=60 |60 < t <= 180 |180 < t |
| 5 > u | | | | | | | |

## Voltage Dips

A voltage dip is a sudden reduction of the RMS voltage below 90% of the nominal value, followed by a return to a value higher than 90% of the nominal in a time varying from 10 ms to 60 s.

## Method of Evaluation

A voltage dip is counted as one polyphase event regardless of the shape and of the number of phases affected (IEC 61000-4-30). An event can begin on one phase and end on another phase. The fault magnitude is recorded separately for each phase involved. The event duration is measured from the instant at which the voltage falls below the start threshold on one of the phases to that at which it becomes greater than the end threshold on all affected phases including a threshold hysteresis.

Time aggregation of multiple successive voltage dips can be applied.

The basic voltage dip measurement is Urms(1/2).

## Statistical Survey

The PM180 provides statistical evaluation of voltage dips using the classification recommended by EN 50160:2010. Dips are classified by residual voltage magnitude and duration according to Table A-4.

Table A-4 Classification of dips according to residual voltage and duration
| Residual voltage, u %Un |Duration t, s | | | | |
| |0.01 <= t <= 0.2 |0.2 < t <= 0.5 |0.5 < t <= 1 |1 < t <= 5 |5 < t <= 60 |
| 90 > u >= 80 | | | | | |
| 80 > u >= 70 | | | | | |
| 70 > u >= 40 | | | | | |
| 40 > u >= 5 | | | | | |
| 5 > u | | | | | |

## Voltage Swells

Voltage swells are sudden rises of the voltage RMS value of more than 110% of nominal voltage. Voltage swells may last between 10 milliseconds and one minute.

## Method of Evaluation

A swell is counted as one polyphase event regardless of the shape and of the number of phases affected (IEC 61000-4-30). An event can begin on one phase and end on another phase. The fault magnitude is recorded separately for each phase involved. The event duration is measured from the instant at which the voltage rises above the start threshold on one of the phases to that at which it becomes lower than the end threshold on all affected phases including a threshold hysteresis.

Time aggregation of multiple successive voltage swells can be applied.

The basic voltage measurement is Urms(1/2).

## Statistical Survey

The PM180 provides statistical evaluation of voltage swells using the classification recommended by EN 50160:2010. Swells are classified by voltage magnitude and duration according to Table A-5.

Table A-5 Classification of swells according to maximum voltage and duration
| Swell voltage, u %Un |Duration t, s | | |
| |0.01 <= t <= 0.5 |0.5 < t <= 5 |5 < t <= 60 |
| u >= 120 | | | |
| 120 > u > 110 | | | |

## Transient Overvoltages

Transient overvoltages correspond to disturbances of very short duration, lasting typically less than one half-cycle, i.e. a few microseconds to several milliseconds.

## Method of Evaluation

Transient overvoltages are detected as impulsive or low frequency oscillatory transients with a rise time less than 0.5 ms and duration from 20 us with the fast transient module option and from 75 us without it, and up to a half cycle. The impulse magnitude is referenced to the nominal voltage amplitude (1.414 Un). The meter can detect transient overvoltages with a magnitude of up to 2 kV with the fast transient module option or up to 700V without it.

## Statistical Survey

Statistical data is classified by transient magnitude and duration. EN 50160:2010 does not provide a classification method for transient overvoltages. The PM180 EN 50160:2010 PQ classifies transient overvoltages according to Table A-6.

Table A-6 Classification of transient overvoltages according to magnitude and duration
| Transient voltage, u %Un peak |Duration t, ms | | | | | |
| |t <= 0.1 |0.1 < t <= 0.2 |0.2 < t <= 0.5 |0.5 < t <= 1 |1 < t <= 5 |5 < t <= 10 |
| u > 800 | | | | | | |
| 800 >= u > 400 | | | | | | |
| 400 >= u > 200 | | | | | | |
| 200 >= u > 100 | | | | | | |
| 100 >= u > 20 | | | | | | |

## Annex B EN 50160:2010 Compliance Statistics Log

Annex B EN 50160:2010 Compliance Statistics Log
| Field No. |Field Label |Description |
| | |Section 0 - Frequency Variation |
| 1 |Nnv |Number of non-valid 10-sec intervals |
| 2 |N |Number of valid 10-sec intervals |
| 3 |N1 |Number of values exceeded percentile limit |
| 4 |N2 |Number of values exceeded maximum permissible limit |
| 5 |df min1 |Low percentile of frequency variation, +/-%Fn |
| 6 |df max1 |High percentile of frequency variation, +/-%Fn |
| 7 |df min2 |Minimum frequency variation, +/-%Fn |
| 8 |df max2 |Maximum frequency variation, +/-%Fn |
| 9 |df lim1 low |Low percentile limit of frequency variation, %Fn |
| 10 |df lim1 high |High percentile limit of frequency variation, %Fn |
| 11 |df lim2 low |Low maximum limit of frequency variation, %Fn |
| 12 |df lim2 high |High maximum limit of frequency variation, %Fn |
| 13 |PercRank |Compliance percentile rank, % |
| | |Section 1 - Voltage Variations |
| 1 |Nnv |Number of non-valid 10-min intervals |
| 2 |N |Number of valid 10-min intervals |
| 3 |V1 N1 |Number of values exceeded percentile limit on phase A/AB |
| 4 |V1 N2 |Number of values exceeded maximum limit on phase A/AB |
| 5 |V1 dU min1 |Low percentile of voltage variation on phase A/AB, +/-%Un |
| 6 |V1 dU max1 |High percentile of voltage variation on phase A/AB, +/-%Un |
| 7 |V1 dU min2 |Minimum voltage variation on phase A/AB, +/-%Un |
| 8 |V1 dU max2 |Maximum voltage variation on phase A/AB, +/-%Un |
| 9 |V2 N1 |Number of values exceeded percentile limit on phase B/BC |
| 10 |V2 N2 |Number of values exceeded maximum limit on phase B/BC |
| 11 |V2 dU min1 |Low percentile of voltage variation on phase B/BC, +/-%Un |
| 12 |V2 dU max1 |High percentile of voltage variation on phase B/BC, +/-%Un |
| 13 |V2 dU min2 |Minimum voltage variation on phase B/BC, +/-%Un |
| 14 |V2 dU max2 |Maximum voltage variation on phase B/BC, +/-%Un |
| 15 |V3 N1 |Number of values exceeded percentile limit on phase C/CA |
| 16 |V3 N2 |Number of values exceeded maximum limit on phase C/CA |
| 17 |V3 dU min1 |Low percentile of voltage variation on phase C/CA, +/-%Un |
| 18 |V3 dU max1 |High percentile of voltage variation on phase C/CA, +/-%Un |
| 19 |V3 dU min2 |Minimum voltage variation on phase C/CA, +/-%Un |
| 20 |V3 dU max2 |Maximum voltage variation on phase C/CA, +/-%Un |
| 21 |dU lim1 low |Low percentile limit of voltage variation, %Un |
| 22 |dU lim1 high |High percentile limit of voltage variation, %Un |
| 23 |dU lim2 low |Low maximum limit of voltage variation, %Un |
| 24 |dU lim2 high |High maximum limit of voltage variation, %Un |
| 25 |PercRank |Compliance percentile rank, % |
| | |Section 2 - Rapid Voltage Changes |
| 1 |N1 |Number of polyphase incidents |
| 2 |V1 N1 |Number of incidents on phase A/AB |
| 3 |V1 dU |Maximum voltage change on phase A/AB, %Un |
| 4 |V2 N1 |Number of incidents on phase B/BC |
| 5 |V2 dU |Maximum voltage change on phase B/BC, %Un |
| 6 |V3 N1 |Number of incidents on phase C/CA |
| 7 |V3 dU |Maximum voltage change on phase C/CA, %Un |
| 8 |dU lim |Maximum permissible limit of voltage changes, Un% |
| | |Section 3 - Flicker |
| 1 |Nnv |Number of non-valid 2-hour intervals |
| 2 |N |Number of valid 2-hour intervals |
| 3 |V1 Plt N1 |Number of Plt values exceeded percentile limit on phase A/AB |
| 4 |V1 Plt max1 |High percentile of Plt on phase A/AB |
| 5 |V1 Plt max2 |Maximum Plt on phase A/AB |
| 6 |V2 Plt N1 |Number of Plt values exceeded percentile limit on phase B/BC |
| 7 |V2 Plt max1 |High percentile of Plt on phase B/BC |
| 8 |V2 Plt max2 |Maximum Plt on phase B/BC |
| 9 |V3 Plt N1 |Number of Plt values exceeded percentile limit on phase C/CA |
| 10 |V3 Plt max1 |High percentile of Plt on phase C/CA |
| 11 |V3 Plt max2 |Maximum Plt on phase C/CA |
| 12 |Plt lim |High percentile limit of Plt |
| 13 |PercRank |Compliance percentile rank, % |
| | |Section 4 - Voltage Unbalance |
| 1 |Nnv |Number of non-valid 10-min intervals |
| 2 |N |Number of valid 10-min intervals |
| 3 |Vunb N1 |Number of voltage unbalance values exceeded percentile limit |
| 4 |Vunb max1 |High percentile of voltage unbalance, % |
| 5 |Vunb max2 |Maximum voltage unbalance, % |
| 6 |Vunb lim |High percentile limit of voltage unbalance, % |
| 7 |PercRank |Compliance percentile rank, % |
| | |Section 5 - Voltage THD |
| 1 |Nnv |Number of non-valid 10-min intervals |
| 2 |N |Number of valid 10-min intervals |
| 3 |V1 N1 |Number of THD values exceeded percentile limit on phase A/AB |
| 4 |V1 THD max1 |High percentile of THD on phase A/AB, % |
| 5 |V1 THD max2 |Maximum THD on phase A/AB, % |
| 6 |V2 N1 |Number of THD values exceeded percentile limit on phase B/BC |
| 7 |V2 THD max1 |High percentile of THD on phase B/BC, % |
| 8 |V2 THD max2 |Maximum THD on phase B/BC, % |
| 9 |V3 N1 |Number of THD values exceeded percentile limit on phase C/CA |
| 10 |V3 THD max1 |High percentile of THD on phase C/CA, % |
| 11 |V3 THD max2 |Maximum THD on phase C/CA, % |
| 12 |THD lim |High percentile limit of THD, % |
| 13 |PercRank |Compliance percentile rank, % |
| | |Section 6 - Signaling Voltage |
| 1 |Nnv |Number of non-valid intervals |
| 2 |N |Number of valid intervals |
| 3 |V1 Sig1 N1 |Number of 1st signaling voltage incidents on phase A/AB |
| 4 |V1 Sig1 |Maximum 1st signaling voltage magnitude on phase A/AB, %Un |
| 5 |V1 Sig2 N1 |Number of 2nd signaling voltage incidents on phase A/AB |
| 6 |V1 Sig2 |Maximum 2nd signaling voltage magnitude on phase A/AB, %Un |
| 7 |V1 Sig3 N1 |Number of 3rd signaling voltage incidents on phase A/AB |
| 8 |V1 Sig3 |Maximum 3rd signaling voltage magnitude on phase A/AB, %Un |
| 9 |V1 Sig4 N1 |Number of 4th signaling voltage incidents on phase A/AB |
| 10 |V1 Sig4 |Maximum 4th signaling voltage magnitude on phase A/AB, %Un |
| 11 |V2 Sig1 N1 |Number of 1st signaling voltage incidents on phase B/BC |
| 12 |V2 Sig1 |Maximum 1st signaling voltage magnitude on phase B/BC, %Un |
| 13 |V2 Sig2 N1 |Number of 2nd signaling voltage incidents on phase B/BC |
| 14 |V2 Sig2 |Maximum 2nd signaling voltage magnitude on phase B/BC, %Un |
| 15 |V2 Sig3 N1 |Number of 3rd signaling voltage incidents on phase B/BC |
| 16 |V2 Sig3 |Maximum 3rd signaling voltage magnitude on phase B/BC, %Un |
| 17 |V2 Sig4 N1 |Number of 4th signaling voltage incidents on phase B/BC |
| 18 |V2 Sig4 |Maximum 4th signaling voltage magnitude on phase B/BC, %Un |
| 19 |V3 Sig1 N1 |Number of 1st signaling voltage incidents on phase C/CA |
| 20 |V3 Sig1 |Maximum 1st signaling voltage magnitude on phase C/CA, %Un |
| 21 |V3 Sig2 N1 |Number of 2nd signaling voltage incidents on phase C/CA |
| 22 |V3 Sig2 |Maximum 2nd signaling voltage magnitude on phase C/CA, %Un |
| 23 |V3 Sig3 N1 |Number of 3rd signaling voltage incidents on phase C/CA |
| 24 |V3 Sig3 |Maximum 3rd signaling voltage magnitude on phase C/CA, %Un |
| 25 |V3 Sig4 N1 |Number of 4th signaling voltage incidents on phase C/CA |
| 26 |V3 Sig4 |Maximum 4th signaling voltage magnitude on phase C/CA, %Un |
| 27 |Sig1 frq |1st signaling frequency |
| 28 |Sig2 frq |2nd signaling frequency |
| 29 |Sig3 frq |3rd signaling frequency |
| 30 |Sig4 frq |4th signaling frequency |
| 31 |V Sig1 lim |Maximum permissible 1st signaling voltage magnitude, %Un |
| 32 |V Sig2 lim |Maximum permissible 2nd signaling voltage magnitude, %Un |
| 33 |V Sig3 lim |Maximum permissible 3rd signaling voltage magnitude, %Un |
| 34 |V Sig4 lim |Maximum permissible 4th signaling voltage magnitude, %Un |
| 35 |PercRank |Compliance percentile rank, % |
| | |Section 7 - Voltage Interruptions (indicative statistics) |
| 1 |N1 0,5s |Number of short polyphase interruptions <=500ms |
| 2 |N2 1s |Number of short polyphase interruptions <=1s |
| 3 |N3 5s |Number of short polyphase interruptions <=5s |
| 4 |N4 20s |Number of short polyphase interruptions <=20s |
| 5 |N5 60s |Number of short polyphase interruptions <=60s |
| 6 |N6 180s |Number of short polyphase interruptions <=180s |
| 7 |N7 >180s |Number of long polyphase interruptions >180s |
| 8 |V min |Minimum residual voltage, %Un |
| 9 |dt max |Maximum duration of a short polyphase interruption |
| 10 |dt tot |Total duration of short polyphase interruptions |
| | |Section 8 - Voltage Dips (indicative statistics) |
| 1 |N11 90%/0,2s |Number of polyphase dips <90% and duration <=0.2 s |
| 2 |N12 90%/0,5s |Number of polyphase dips <90% and duration <=0.5 s |
| 3 |N13 90%/1s |Number of polyphase dips <90% and duration <=1 s |
| 4 |N14 90%/5s |Number of polyphase dips <90% and duration <=5 s |
| 5 |N15 90%/60s |Number of polyphase dips <90% and duration <=60 s |
| 6 |N21 80%/0,2s |Number of polyphase dips <80% and duration <=0.2 s |
| 7 |N22 80%/0,5s |Number of polyphase dips <80% and duration <=0.5 s |
| 8 |N23 80%/1s |Number of polyphase dips <80% and duration <=1 s |
| 9 |N24 80%/5s |Number of polyphase dips <80% and duration <=5 s |
| 10 |N25 80%/60s |Number of polyphase dips <80% and duration <=60 s |
| 11 |N31 70%/0,2s |Number of polyphase dips <70% and duration <=0.2 s |
| 12 |N32 70%/0,5s |Number of polyphase dips <70% and duration <=0.5 s |
| 13 |N33 70%/1s |Number of polyphase dips <70% and duration <=1 s |
| 14 |N34 70%/5s |Number of polyphase dips <70% and duration <=5 s |
| 15 |N35 70%/60s |Number of polyphase dips <70% and duration <=60 s |
| 16 |N41 40%/0,2s |Number of polyphase dips <40% and duration <=0.2 s |
| 17 |N42 40%/0,5s |Number of polyphase dips <40% and duration <=0.5 s |
| 18 |N43 40%/1s |Number of polyphase dips <40% and duration <=1 s |
| 19 |N44 40%/5s |Number of polyphase dips <40% and duration <=5 s |
| 20 |N45 40%/60s |Number of polyphase dips <40% and duration <=60 s |
| 21 |N51 5%/0,2s |Number of polyphase dips <5% and duration <=0.2 s |
| 22 |N52 5%/0,5s |Number of polyphase dips <5% and duration <=0.5 s |
| 23 |N53 5%/1s |Number of polyphase dips <5% and duration <=1 s |
| 24 |N54 5%/5s |Number of polyphase dips <5% and duration <=5 s |
| 25 |N55 5%/60s |Number of polyphase dips <5% and duration <=60 s |
| 26 |dt max 90% |Maximum duration of a polyphase dip < 90% |
| 27 |dt max 85% |Maximum duration of a polyphase dip < 80% |
| 28 |dt max 70% |Maximum duration of a polyphase dip < 70% |
| 29 |dt max 40% |Maximum duration of a polyphase dip < 40% |
| 30 |dt max 10% |Maximum duration of a polyphase dip < 5% |
| 31 |V min 0.2s |Minimum residual voltage of dips with duration <=0.2 s, %Un |
| 32 |V min 0.5s |Minimum residual voltage of dips with duration <=0.5 s, %Un |
| 33 |V min 1s |Minimum residual voltage of dips with duration <=1 s, %Un |
| 34 |V min 5s |Minimum residual voltage of dips with duration <=5 s, %Un |
| 35 |V min 60s |Minimum residual voltage of dips with duration <=60 s, %Un |
| 36 |dt tot |Total duration of polyphase dips |
| | |Section 9 - Voltage Swells (indicative statistics) |
| 1 |N11 120%/0,5s |Number of polyphase swells >=120% and duration <=0.5 s |
| 2 |N12 120%/5s |Number of polyphase swells >=120% and duration <=5 s |
| 3 |N13 120%/60s |Number of polyphase swells >=120% and duration <=60 s |
| 4 |N21 110%/0,5s |Number of polyphase swells >110% and duration <=0.5 s |
| 5 |N22 110%/5s |Number of polyphase swells >110% and duration <=5 s |
| 6 |N23 110%/60s |Number of polyphase swells >110% and duration <=60 s |
| 7 |dt max 120% |Maximum duration of polyphase swells >=120% |
| 8 |dt max 110% |Maximum duration of polyphase swells >110% |
| 9 |V max 0,5s |Maximum polyphase swell voltage with duration <=0.5 s, %Un |
| 10 |V max 5s |Maximum polyphase swell voltage with duration <=5 s, %Un |
| 11 |V max 60s |Maximum polyphase swell voltage with duration <=60 s, %Un |
| 12 |dt tot |Total duration of polyphase swells |
| | |Section 10 - Transient Overvoltages (indicative statistics) |
| 1 |N11 20%/0,1ms |Number of polyphase impulses >20% and duration <=0.1 ms |
| 2 |N12 20%/0,2ms |Number of polyphase impulses >20% and duration <=0.2 ms |
| 3 |N13 20%/0,5ms |Number of polyphase impulses >20% and duration <=0.5 ms |
| 4 |N14 20%/1ms |Number of polyphase impulses >20% and duration <=1 ms |
| 5 |N15 20%/5ms |Number of polyphase impulses >20% and duration <=5 ms |
| 6 |N16 20%/10ms |Number of polyphase impulses >20% and duration <=10 ms |
| 7 |N21 100%/0,1ms |Number of polyphase impulses >100% and duration <=0.1 ms |
| 8 |N22 100%/0,2ms |Number of polyphase impulses >100% and duration <=0.2 ms |
| 9 |N23 100%/0,5ms |Number of polyphase impulses >100% and duration <=0.5 ms |
| 10 |N24 100%/1ms |Number of polyphase impulses >100% and duration <=1 ms |
| 11 |N25 100%/5ms |Number of polyphase impulses >100% and duration <=5 ms |
| 12 |N26 100%/10ms |Number of polyphase impulses >100% and duration <=10 ms |
| 13 |N31 200%/0,1ms |Number of polyphase impulses >200% and duration <=0.1 ms |
| 14 |N32 200%/0,2ms |Number of polyphase impulses >200% and duration <=0.2 ms |
| 15 |N33 200%/0,5ms |Number of polyphase impulses >200% and duration <=0.5 ms |
| 16 |N34 200%/1ms |Number of polyphase impulses >200% and duration <=1 ms |
| 17 |N35 200%/5ms |Number of polyphase impulses >200% and duration <=5 ms |
| 18 |N36 200%/10ms |Number of polyphase impulses >200% and duration <=10 ms |
| 19 |N41 400%/0,1ms |Number of polyphase impulses >400% and duration <=0.1 ms |
| 20 |N42 400%/0,2ms |Number of polyphase impulses >400% and duration <=0.2 ms |
| 21 |N43 400%/0.5ms |Number of polyphase impulses >400% and duration <=0.5 ms |
| 22 |N44 400%/1ms |Number of polyphase impulses >400% and duration <=1 ms |
| 23 |N45 400%/5ms |Number of polyphase impulses >400% and duration <=5 ms |
| 24 |N46 400%/10ms |Number of polyphase impulses >400% and duration <=10 ms |
| 25 |N51 800%/0,1ms |Number of polyphase impulses >800% and duration <=0.1 ms |
| 26 |N52 800%/0,2ms |Number of polyphase impulses >800% and duration <=0.2 ms |
| 27 |N53 800%/0.5ms |Number of polyphase impulses >800% and duration <=0.5 ms |
| 28 |N54 800%/1ms |Number of polyphase impulses >800% and duration <=1 ms |
| 29 |N55 800%/5ms |Number of polyphase impulses >800% and duration <=5 ms |
| 30 |N56 800%/10ms |Number of polyphase impulses >800% and duration <=10 ms |
| 31 |V max 0,1ms |Maximum impulsive voltage with duration <=0.1 ms, %Un peak |
| 32 |V max 0,2ms |Maximum impulsive voltage with duration <=0.2 ms, %Un peak |
| 33 |V max 0,5ms |Maximum impulsive voltage with duration <=0.5 ms, %Un peak |
| 34 |V max 1ms |Maximum impulsive voltage with duration <=1 ms, %Un peak |
| 35 |V max 5ms |Maximum impulsive voltage with duration <=5 ms, %Un peak |
| 36 |V max 10ms |Maximum impulsive voltage with duration <=10 ms, %Un peak |

## Annex C EN 50160:2010 Harmonics Compliance Statistics Log

Annex C EN 50160:2010 Harmonics Compliance Statistics Log
| Field No. |Field Label |Description |
| | |Section 0 – V1 Harmonic Compliance |
| 1 |Nnv |Number of non-valid 10-min intervals |
| 2 |N |Number of valid 10-min intervals |
| 3 |H02 N1 |Number of H02 values exceeded percentile limit on phase A/AB |
| 4 |H03 N1 |Number of H03 values exceeded percentile limit on phase A/AB |
| |… | |
| 51 |H50 N1 |Number of H50 values exceeded percentile limit on phase A/AB |
| 52 |PercRank |Compliance percentile rank, % |
| | |Section 1 – V2 Harmonic Compliance |
| 1 |Nnv |Number of non-valid 10-min intervals |
| 2 |N |Number of valid 10-min intervals |
| 3 |H02 N1 |Number of H02 values exceeded percentile limit on phase B/BC |
| 4 |H03 N1 |Number of H03 values exceeded percentile limit on phase B/BC |
| |… | |
| 51 |H50 N1 |Number of H50 values exceeded percentile limit on phase B/BC |
| 52 |PercRank |Compliance percentile rank, % |
| | |Section 2 – V3 Harmonic Compliance |
| 1 |Nnv |Number of non-valid 10-min intervals |
| 2 |N |Number of valid 10-min intervals |
| 3 |H02 N1 |Number of H02 values exceeded percentile limit on phase C/CA |
| 4 |H03 N1 |Number of H03 values exceeded percentile limit on phase C/CA |
| |… | |
| 51 |H50 N1 |Number of H50 values exceeded percentile limit on phase C/CA |
| 52 |PercRank |Compliance percentile rank, % |
| | |Section 3 – V1 Harmonic Voltages |
| 1 |%H02 max1 |High percentile probability value of H02 on phase A/AB, % |
| 2 |%H03 max1 |High percentile probability value of H03 on phase A/AB, % |
| |… | |
| 49 |%H50 max1 |High percentile probability value of H50 on phase A/AB, % |
| 50 |%H02 max2 |Maximum value of H02 on phase A/AB, % |
| 51 |%H03 max2 |Maximum value of H03 on phase A/AB, % |
| |… | |
| 98 |%H50 max2 |Maximum value of H50 on phase A/AB, % |
| | |Section 4 – V2 Harmonic Voltages |
| 1 |%H02 max1 |High percentile probability value of H02 on phase B/BC, % |
| 2 |%H03 max1 |High percentile probability value of H03 on phase B/BC, % |
| |… | |
| 49 |%H50 max1 |High percentile probability value of H50 on phase B/BC, % |
| 50 |%H02 max2 |Maximum value of H02 on phase B/BC, % |
| 51 |%H03 max2 |Maximum value of H03 on phase B/BC, % |
| |… | |
| 98 |%H50 max2 |Maximum value of H50 on phase B/BC, % |
| | |Section 5 – V3 Harmonic Voltages |
| 1 |%H02 max1 |High percentile probability value of H02 on phase C/CA, % |
| 2 |%H03 max1 |High percentile probability value of H03 on phase C/CA, % |
| |… | |
| 49 |%H50 max1 |High percentile probability value of H50 on phase C/CA, % |
| 50 |%H02 max2 |Maximum value of H02 on phase C/CA, % |
| 51 |%H03 max2 |Maximum value of H03 on phase C/CA, % |
| |… | |
| 98 |%H50 max2 |Maximum value of H50 on phase C/CA, % |
| | |Section 6 - V1 Interharmonic Compliance |
| 1 |Nnv |Number of non-valid 10-min intervals |
| 2 |N |Number of valid 10-min intervals |
| 3 |H02 N1 |Number of H02 values exceeded percentile limit on phase A/AB |
| 4 |H03 N1 |Number of H03 values exceeded percentile limit on phase A/AB |
| |… | |
| 51 |H50 N1 |Number of H50 values exceeded percentile limit on phase A/AB |
| 52 |PercRank |Compliance percentile rank, % |
| | |Section 7 – V2 Interharmonic Compliance |
| 1 |Nnv |Number of non-valid 10-min intervals |
| 2 |N |Number of valid 10-min intervals |
| 3 |H02 N1 |Number of H02 values exceeded percentile limit on phase B/BC |
| 4 |H03 N1 |Number of H03 values exceeded percentile limit on phase B/BC |
| |… | |
| 51 |H50 N1 |Number of H50 values exceeded percentile limit on phase B/BC |
| 52 |PercRank |Compliance percentile rank, % |
| | |Section 8 – V3 Interharmonic Compliance |
| 1 |Nnv |Number of non-valid 10-min intervals |
| 2 |N |Number of valid 10-min intervals |
| 3 |H02 N1 |Number of H02 values exceeded percentile limit on phase C/CA |
| 4 |H03 N1 |Number of H03 values exceeded percentile limit on phase C/CA |
| |… | |
| 51 |H50 N1 |Number of H50 values exceeded percentile limit on phase C/CA |
| 52 |PercRank |Compliance percentile rank, % |
| | |Section 9 – V1 Interharmonic Voltages |
| 1 |%H02 max1 |High percentile probability value of H02 on phase A/AB, % |
| 2 |%H03 max1 |High percentile probability value of H03 on phase A/AB, % |
| |… | |
| 49 |%H50 max1 |High percentile probability value of H50 on phase A/AB, % |
| 50 |%H02 max2 |Maximum value of H02 on phase A/AB, % |
| 51 |%H03 max2 |Maximum value of H03 on phase A/AB, % |
| |… | |
| 98 |%H50 max2 |Maximum value of H50 on phase A/AB, % |
| | |Section 10 - V2 Interharmonic Voltages |
| 1 |%H02 max1 |High percentile probability value of H02 on phase B/BC, % |
| 2 |%H03 max1 |High percentile probability value of H03 on phase B/BC, % |
| |… | |
| 49 |%H50 max1 |High percentile probability value of H50 on phase B/BC, % |
| 50 |%H02 max2 |Maximum value of H02 on phase B/BC, % |
| 51 |%H03 max2 |Maximum value of H03 on phase B/BC, % |
| |… | |
| 98 |%H50 max2 |Maximum value of H50 on phase B/BC, % |
| | |Section 11 - V3 Interharmonic Voltages |
| 1 |%H02 max1 |High percentile probability value of H02 on phase C/CA, % |
| 2 |%H03 max1 |High percentile probability value of H03 on phase C/CA, % |
| |… | |
| 49 |%H50 max1 |High percentile probability value of H50 on phase C/CA, % |
| 50 |%H02 max2 |Maximum value of H02 on phase C/CA, % |
| 51 |%H03 max2 |Maximum value of H03 on phase C/CA, % |
| |… | |
| 98 |%H50 max2 |Maximum value of H50 on phase C/CA, % |

## Annex D Online PQ Data

Annex D Online PQ Data
| Field Label |Description |
| |Last recorded EN 50160:2010 voltage incidents data |
| V1 Var% |V1 Voltage variation, +/-%Un |
| V2 Var% |V2 Voltage variation, +/-%Un |
| V3 Var% |V3 Voltage variation, +/-%Un |
| V1 dUss |V1 Steady state voltage change, %Un |
| V1 dUmax |V1 Maximum voltage change, %Un |
| V2 dUss |V2 Steady state voltage change, %Un |
| V2 dUmax |V2 Maximum voltage change, %Un |
| V3 dUss |V3 Steady state voltage change, %Un |
| V4 dUmax |V3 Maximum voltage change, %Un |
| V1 Pst |V1 Voltage Pst |
| V2 Pst |V2 Voltage Pst |
| V3 Pst |V3 Voltage Pst |
| V1 Plt |V1 Voltage Plt |
| V2 Plt |V2 Voltage Plt |
| V3 Plt |V3 Voltage Plt |
| V1 THD |V1 Voltage THD, % |
| V2 THD |V2 Voltage THD, % |
| V3 THD |V3 Voltage THD, % |
| NSeq Unb% |Negative-sequence voltage unbalance, % |
| ZSeq Unb% |Zero-sequence voltage unbalance, % |
| Freq Var% |Frequency variation, +/-%Fn |
| V1 Int |Short voltage interruption, V1 residual voltage, %Un |
| V2 Int |Short voltage interruption, V2 residual voltage, %Un |
| V3 Int |Short voltage interruption, V3 residual voltage, %Un |
| Int dt |Short voltage interruption, duration, ms |
| V1 Dip |Voltage dip, V1 residual voltage, %Un |
| V2 Dip |Voltage dip, V2 residual voltage, %Un |
| V3 Dip |Voltage dip, V3 residual voltage, %Un |
| Dip dt |Voltage dip, duration, ms |
| V1 Swl |Voltage swell, V1 voltage, %Un |
| V2 Swl |Voltage swell, V2 voltage, %Un |
| V3 Swl |Voltage swell, V2 voltage, %Un |
| Swl dt |Voltage swell, duration, ms |
| V1 Imp |V1 Transient overvoltage, %Un peak |
| V1 Imp dt |V1 Transient duration, µs |
| V2 Imp |V2 Transient overvoltage, %Un peak |
| V2 Imp dt |V2 Transient duration, µs |
| V3 Imp |V3 Transient overvoltage, %Un peak |
| V3 Imp dt |V3 Transient duration, µs |
| V1 Sig% |V1 signaling voltage, %Un |
| V2 Sig% |V2 signaling voltage, %Un |
| V3 Sig% |V3 signaling voltage, %Un |
| |Present IEC 61000-4-30 measurements and indication data |
| V1 rms(1/2) |V1 rms(1/2) commencing at fundamental zero crossing |
| V2 rms(1/2) |V2 rms(1/2) commencing at fundamental zero crossing |
| V3 rms(1/2) |V3 rms(1/2) commencing at fundamental zero crossing |
| V1 rms(1/2) Tm |V1 rms(1/2) timestamp, seconds |
| V1 rms(1/2) Tmmcs |V1 rms(1/2) timestamp, fractional second, µs |
| V2 rms(1/2) Tm |V2 rms(1/2) timestamp, seconds |
| V2 rms(1/2) Tmmcs |V2 rms(1/2) timestamp, fractional second, µs |
| V3 rms(1/2) Tm |V3 rms(1/2) timestamp, seconds |
| V3 rms(1/2) Tmmcs |V3 rms(1/2) timestamp, fractional second, µs |
| I1 rms(1/2) |I1 rms(1/2) coincident current |
| I2 rms(1/2) |I2 rms(1/2) coincident current |
| I3 rms(1/2) |I3 rms(1/2) coincident current |
| 10/12c Tm |10/12-cycle block timestamp, seconds |
| 10/12c Tmmcs |10/12-cycle block timestamp, fractional second |
| 10/12c BlockNo |10/12-cycle block number (1-3000) |
| 150/180c BlockNo |150/180-cycle block number (1-200) |
| 10/12c Flag |10/12-cycle interval flag (0=valid, 1=flagged) |
| 150/180c Flag |150/180-cycle interval flag (0=valid, 1=flagged) |
| 10s Flag |10-s interval flag (0=valid, 1=flagged) |
| 10m Flag |10-min interval flag (0=valid, 1=flagged) |
| 2h Flag |2-hour interval flag (0=valid, 1=flagged) |

## Annex E Generic Parameters Group

Annex E Generic Parameters Group
| Field Label |Description |
| V1 |V1 voltage |
| V2 |V2 voltage |
| V3 |V3 voltage |
| V4 |V4 voltage |
| V12 |V12 voltage |
| V23 |V23 voltage |
| V31 |V31 voltage |
| I1 |I1 current |
| I2 |I2 current |
| I3 |I3 current |
| I4 |I4 current |
| In |In current |
| I1x |I1x current (extended range) |
| I2x |I2x current (extended range) |
| I3x |I3x current (extended range) |
| I4x |I4x current (extended range) |
| Inx |Inx current (extended range) |
| V ZERO-SEQ |Zero-sequence voltage |
| I ZERO-SEQ |Zero-sequence current |
| Ix ZERO-SEQ |Ix Zero-sequence current (extended range) |
| V UNB% |Voltage unbalance |
| I UNB% |Current unbalance |
| Ix UNB% |Ix current unbalance (extended range) |
| FREQ |Frequency |
| V1 THD |V1 THD |
| V2 THD |V2 THD |
| V3 THD |V3 THD |
| V4 THD |V4 THD |
| I1 THD |I1 THD |
| I2 THD |I2 THD |
| I3 THD |I3 THD |
| I4 THD |I4 THD |
| V1 THD/I |V1 interharmonic THD |
| V2 THD/I |V2 interharmonic THD |
| V3 THD/I |V3 interharmonic THD |
| V4 THD/I |V4 interharmonic THD |
| I1 THD/I |I1 interharmonic THD |
| I2 THD/I |I2 interharmonic THD |
| I3 THD/I |I3 interharmonic THD |
| I4 THD/I |I4 interharmonic THD |
| I1 TDD |I1 TDD |
| I2 TDD |I2 TDD |
| I3 TDD |I3 TDD |
| I4 TDD |I4 TDD |
| I1 KF |I1 K-Factor |
| I2 KF |I2 K-Factor |
| I3 KF |I3 K-Factor |
| I4 KF |I4 K-Factor |
| V1 CF |V1 Crest Factor |
| V2 CF |V2 Crest Factor |
| V3 CF |V3 Crest Factor |
| V4 CF |V4 Crest Factor |
| I1 CF |I1 Crest Factor |
| I2 CF |I2 Crest Factor |
| I3 CF |I3 Crest Factor |
| I4 CF |I4 Crest Factor |
| V1 rms(1/2) |V1 rms(1/2), commencing at fundamental zero crossing |
| V2 rms(1/2) |V2 rms(1/2), commencing at fundamental zero crossing |
| V3 rms(1/2) |V3 rms(1/2), commencing at fundamental zero crossing |
| I1 rms(1/2) |I1 rms(1/2) coincident current |
| I2 rms(1/2) |I2 rms(1/2) coincident current |
| I3 rms(1/2) |I3 rms(1/2) coincident current |
| V1 Sig% |V1 signaling voltage magnitude, %Un |
| V2 Sig% |V2 signaling voltage magnitude, %Un |
| V3 Sig% |V3 signaling voltage magnitude, %Un |

## Annex F EN 50160:2010 PQ Event Log Report

Sample EN 50160:2010 PQ event log report (screenshot). Drawing not reproduced on this page. [See page 33 of the PDF](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf#page=33).

## Annex G EN 50160:2010 Compliance Report

Sample EN 50160:2010 Compliance Report, report page 1: Tables 1-6 (screenshot). Drawing not reproduced on this page. [See page 34 of the PDF](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf#page=34).

Sample EN 50160:2010 Compliance Report, report page 2: Tables 7-8 (screenshot). Drawing not reproduced on this page. [See page 35 of the PDF](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf#page=35).

Sample EN 50160:2010 Compliance Report, report page 3: Tables 8 (continued)-11 (screenshot). Drawing not reproduced on this page. [See page 36 of the PDF](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf#page=36).

Sample EN 50160:2010 Compliance Report, report page 4: Tables 12-13 (screenshot). Drawing not reproduced on this page. [See page 37 of the PDF](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf#page=37).

## Downloads and related

- [Download the PDF (BB0180 REV.A1, 1151 KB)](https://satec-global.com.au/documentation/PM180-EN50160-2010-Application-Note.pdf)
- [Read the PDF in the document library](https://satec-global.com.au/support/documents/doc-35bc10444c03/)
- [Product support: answers, documents and videos](https://satec-global.com.au/support/products/pm180/)
- [All application notes as web pages](https://satec-global.com.au/support/application-notes/)
- [How do I replace the backup battery in a PM180?](https://satec-global.com.au/support/articles/pm180-battery-replacement/)
- [Which PM180 display and options are fitted or required?](https://satec-global.com.au/support/articles/pm180-display-and-options/)
- [What information and records should I preserve before a PM180 service or change?](https://satec-global.com.au/support/articles/pm180-preserve-before-service-or-change/)

Questions about this document? Use the [contact form](https://satec-global.com.au/contact/).